Determines individual kVA/MVA loading, percentage load factors, and maximum safe total load between two parallel transformers, verifying that neither unit exceeds its thermal rating due to percentage impedance mismatch.
Governing Formulas & Standards
Standards Basis: IEC 60076-8 / IEEE C57.12.00
S_1 = S_{load} \cdot \frac{S_{1,rated} / Z_{1\%}}{\frac{S_{1,rated}}{Z_{1\%}} + \frac{S_{2,rated}}{Z_{2\%}}} \quad ; \quad S_2 = S_{load} - S_1
Load divides inversely proportional to per-unit impedance on a common base; the unit with lower percentage impedance draws disproportionately more load.
Worked Engineering Example: Paralleling 25 MVA (8% Z) and 15 MVA (7.5% Z) under 35 MVA Total Load
- Admittance Weightings: Y1 = 25 / 8.0 = 3.125 ; Y2 = 15 / 7.5 = 2.0 ; Total Y = 5.125 → Y1 = 3.125, Y2 = 2.0
- Load Sharing: S1 = 35 × (3.125 / 5.125) = 21.34 MVA ; S2 = 35 × (2.0 / 5.125) = 13.66 MVA → S1 = 21.34 MVA (85.4% load), S2 = 13.66 MVA (91.1% load)
Final Solution: Transformer 1: 21.34 MVA (85.4%) | Transformer 2: 13.66 MVA (91.1%) | Both within thermal rating.
Frequently Asked Questions
- What happens if two transformers in parallel have different vector groups?
- Paralleling transformers with different vector groups (e.g. Dyn11 and Dyn5, which have a 180° phase angle difference) will cause a catastrophic dead short-circuit across the secondary bus with massive electrodynamic forces.
Interactive calculation engine and real-time CAD solver available online at https://amithvijayan.in/tools/transformer-parallel-sharing.