Current Transformer (CT) Sizing & Knee-Point Voltage Calculator

Standard: IEC 61869-2 (formerly IEC 60044-1) / IEEE Std C37.110 • Discipline: Power System Protection

Determines required Current Transformer (CT) knee-point voltage (Vk), total secondary loop burden resistance (Rct + 2·Rlead + Rrelay), and verifies that protection CTs (Class 5P20, Class PS / PX, or IEEE C-Class) will not saturate under maximum through-fault current and system DC offset X/R.

Governing Formulas & Standards

Standards Basis: IEC 61869-2 (formerly IEC 60044-1) / IEEE Std C37.110

V_k \ge K \cdot I_{sc,sec} \cdot (R_{ct} + 2 R_{lead} + R_{relay}) \quad ; \quad I_{sc,sec} = I_{sc,pri} \times \left(\frac{I_{sec}}{I_{pri}}\right)

Calculates required CT knee-point voltage V_k (V) where K is protection security factor (typically 2.0 for differential/distance protection, or 1 + X/R for transient dimensioning), I_sc,sec is maximum secondary fault current, and R is total loop resistance in ohms.

Worked Engineering Example: Sizing 1200/1 A Class PS CT for Feeder Protection (25 kA Fault Level)

  1. Secondary Fault Current: I_sc,sec = 25,000 × (1 / 1200) → 20.83 A
  2. Total Secondary Loop Resistance: R_total = R_ct + 2×R_lead + R_relay = 4.5 + 0.92 + 0.10 → 5.52 Ω
  3. Required Knee-Point Voltage (Vk): V_k = 2.0 × 20.83 × 5.52 → 229.96 V

Final Solution: Recommended Knee-Point Voltage: Vk ≥ 250 V (at Imag ≤ 30 mA) | Total Loop Burden: 5.52 Ω

Frequently Asked Questions

What is the knee-point voltage of a Current Transformer?
The knee-point voltage (Vk) is the point on the excitation curve where a 10% increase in secondary RMS voltage produces a 50% increase in magnetizing current. Above Vk, the CT core enters severe magnetic saturation and distorts secondary current.
Why are 1 A CTs superior to 5 A CTs for long outdoor switchyard runs?
Because cable burden scales with the square of secondary current (P = I²R). A 5 A CT produces 25× higher lead resistance voltage drop and burden VA than a 1 A CT over identical 100m cable runs, requiring drastically larger copper cables or impractically massive CT cores.

Interactive calculation engine and real-time CAD solver available online at https://amithvijayan.in/tools/ct-sizing-calculator.

Amith Vijayan | Power Systems Engineer & Grid Strategist

12+ years engineering reliable electrical grids, reducing AT&C distribution losses, and deploying 244 precision engineering calculators and CAD simulation suites.

Power Systems Operations, AMI & Loss Reduction

Over a 12-year engineering career in power distribution and utility operations at Kerala State Electricity Board Ltd (KSEBL), Amith Vijayan, CEng, has driven regional transmission and distribution performance to 99.9% reliability, implemented advanced automated metering infrastructure (AMI), and systematically reduced AT&C technical and commercial losses.

  • Chartered Engineer (CEng) certified by The Institution of Engineers (India) (IEI)
  • 99.9% grid reliability sustained across regional distribution networks
  • 15% non-technical losses reduced through automated telemetry and smart metering audits
  • 8.6% technical losses sustained through feeder optimization and conductor reconductoring
  • 500+ engineers, utility technicians, and community members trained in energy conservation and substation safety
  • Invited Keynote Speaker at CIRED 2019 (Madrid, Spain) on Smart Grid Digitisation and Distribution Strategies

44 Precision Electrical & Power Engineering Calculators

Free, client-side, standards-compliant engineering calculators designed for utility engineers, power system planners, and clean energy developers:

1. Residential & Prosumer Sizing

2. Power Systems & Sizing

3. Substations & Assets

4. Clean Energy & Storage

Publications & Industry Books

"When Sparks Become Soul: A Memoir of Struggle, Resilience, and High-Voltage Transformation"

Published memoir chronicling personal and engineering resilience through electrical utility challenges. Available on Amazon.

"Unleashing the Power of Advanced Metering Infrastructure: A Comprehensive Guide for Electric Utilities"

Comprehensive utility project guide detailing AMI planning, meter head-end procurement, cybersecurity, and consumer analytics.